Contact Us | Language: čeština English
Title: | Further experimental results on modelling and algebraic control of a delayed looped heating-cooling process under uncertainties | ||||||||||
Author: | Pekař, Libor; Matušů, Radek; Dostálek, Petr; Song, Mengjie | ||||||||||
Document type: | Peer-reviewed article (English) | ||||||||||
Source document: | Heliyon. 2023, vol. 9, issue 8 | ||||||||||
ISSN: | 2405-8440 (Sherpa/RoMEO, JCR) | ||||||||||
Journal Impact
This chart shows the development of journal-level impact metrics in time
|
|||||||||||
DOI: | https://doi.org/10.1016/j.heliyon.2023.e18445 | ||||||||||
Abstract: | The aim of this research is to revise and substantially extend experimental modelling and control of a looped heating-cooling laboratory process with long input-output and internal delays under uncertainties. This research follows and extends the authors' recent results. As several significant improvements regarding robust modelling and control have been reached, the obtained results are provided with a link and comparison to the previous findings. First, an infinite-dimensional model based on mathematical-physical heat and mass transfer principles is developed. All important heat-fluid transport and control-signal delays are considered when assembling the model structure and relations of quantities. Model parameter values optimization based on the measurement data follows. When determining static model parameter values, all variations in steady-state measured data are taken into account simultaneously, which enhances previously obtained models. Values of dynamic model parameters and delays are further obtained by least mean square optimization. This innovative model is compared to two recently developed process models and to the best-fit model that ignores the measured variations. Controller structures are designed using algebraic tools for all four models. The designed controllers are robust in the sense of robust stability and performance. Both concepts are rigorously assessed, and the obtained conditions serve for controller parameter tuning. Two different control systems are assumed: the standard closed-loop feedback loop and the two-feedback-controllers control system. Numerous experimental measurements for nominal conditions and selected perturbations are performed. Obtained results are further analyzed via several criteria on manipulated input and controlled temperature. The designed controllers are compared to the Smith predictor structure that is wellestablished for time-delay systems control. An essential drawback of the predictor regarding disturbance rejection is highlighted. | ||||||||||
Full text: | https://www.sciencedirect.com/science/article/pii/S2405844023056530 | ||||||||||
Show full item record |